Attribute ‘symbol’ΒΆ

The pragma {attribute 'symbol'} defines which variables of a program or a global variable list are to be adopted into the symbol configuration. This means that the variables are exported as symbols to a symbol list. This symbol list is then available for external access both as an XML file in the project directory and as a file that is invisible to the user on the target system. For example, the symbol list is then available for access by an OPC server. The variables thus equipped with a symbol are loaded by CODESYS to the controller, even if they are not explicitly configured or visible in the editor of the symbol configuration.

In any case, however, an object Symbol configuration must be created below the application concerned in the device tree.

Syntax:

{attribute 'symbol' := '<access possibilities>'}

<access possibilities>: none, read, write, readwrite. The default value readwrite applies if no parameter is specified.

Insertion position:

Example

With the following configuration the variables A and B are exported with read and write permission. Variable D is exported with read permission.

{attribute 'symbol' := 'readwrite'}
PROGRAM PLC_PRG
VAR
 A : INT;
 B : INT;
{attribute 'symbol' := 'none'}
 C : INT;
{attribute 'symbol' := 'read'}
 D : INT;
END_VAR