Configuring Devices and I/O Mapping

Configuring devices

You can configure the device objects inserted into the device tree in the associated device editor. The possibilities depend on the device description. The ‘generic device editor’ provides tabs that are supplemented as necessary by device-specific tabs.

Requirement: You have opened a standard project in whose device tree a standard PLC and below that a fieldbus device object are inserted.

  1. Double-click the device object of the standard PLC in the device tree of your project.

    ⇒ The <device name> editor opens in the CODESYS main window. The Communication settings tab is in the foreground. Change to the other tabs in order to make configuration settings for the controller. Please refer to the help pages for the generic device editor.

  2. Double-click the fieldbus device object in the device tree of your project.

    ⇒ The <fieldbus device name> editor opens in the CODESYS main window. Specific tabs are available depending on the device. For the configuration options, please refer to the help pages for the respective device editor. If the option Show generic device configuration views is activated in Tools ‣ Options , category Device editor, see also the tabs contributed by the generic device editor.

See also

Reading the PLC parameter file into a configuration

If the configuration parameters of the PLC have been changed by another device, for example via a visualization, a configuration file IoConfig.par is created on the controller. Depending on the device, a button may be in the parameter dialog of the device editor in online mode for writing the current parameters to such a file. In order to update the changed parameters inside your project as well, you can read in the parameter file in online mode.

Requirement: You have a standard project with a device tree in which the hardware environment is mapped with a PLC and a parameterizable device in the device tree. On the controller there is a file IoConfig.par, in which the device parameters were previously saved with the current values.

  1. Add the command Read PLC parameter file to configuration from the category Devices in the dialog Tools ‣ Customize to an interface menu.

  2. Select the PLC device object in the device tree and open the context menu.

  3. Select the command Read PLC parameter file to configuration.

    ⇒ CODESYS automatically establishes a connection to the controller and reads in the parameters from the par-file. These are updated accordingly in the tab with the device parameters.

See also

General information about I/O mapping

Whether or not you can configure an I/O mapping to project variables or even to the entire function blocks depends on the type of device. Configuring an I/O map means linking input and output channels of the device with variables of the project. We also use the term ‘mapping’ for this.

Pay attention in general to the following for the mapping of inputs and outputs of a device to variables in CODESYS:

  • You do not have write access to variables that are mapped to an input.

  • You can map an already existing variable to one input only.

  • You can directly generate new global implicit variables in the I/O map and map them to a device channel.

  • The memory layout of structures is specified by the device.

  • You can change addresses and fix values in the I/O map.

  • For each variable that is assigned to an I/O channel in the I/O Mapping dialog, you can cause ‘force variables’ to be generated during the compilation of the application (see further below). Using these variables you can, for example during the commissioning of a plant, force a value on the input or output via a visualization/HMI.

  • Changes in the I/O map can be transferred to the controller with an online change.

  • If a pointer to a device input is used, the access is considered to be a write access, for example pTest := ADR(input);. This leads to a compiler warning when code is generated : “...invalid assignment target”. If you require a construct of this kind, you must first copy the input value input to a variable with write access.

  • An I/O address can also be linked with a variable via the ‘AT declaration’ in the IEC code. Since a device configuration often changes again, however, we recommend that you make the assignments only in the device editor.

    If you use the AT declaration, please pay attention to the following:

    • An AT declaration is permissible only with local or global variables, not with input or output variables of function blocks.
    • Implicit ‘force variables’ for I/Os (see below) cannot be generated for AT declarations.
    • If you use an AT declaration with structure variables or function block variables, all instances will access the same memory location. This then corresponds to the use of ‘static variables’ in classic programming languages such as ‘C’.

Hint

If a pointer to a device input is used, then the access (for example pTest := ADR(input);) is considered to be a write access. This leads to a compiler warning when code is generated : “...invalid assignment target”.

If you require a construct of this kind, you must first copy the input value (input) to a variable with write access.

Note

As an alternative, you can assign a variable to an address in the programming code using the AT declaration. In view of possible changes of the device configuration, however, we recommend that you make the assignments only in the device editor.

Note

You can export the I/O mapping configuration of a device to a csv file or import it from such a file.

See also

Linking a device input with an existing project variable (“Mapping”)

Requirement: A device that supports an I/O mapping configuration in CODESYS is inserted in the device tree of your project. On the I/O Mapping tab in the device editor you thus get a tabular display of the input and output channels of the device with specification of the addresses and data types.

Hint

Mapping ‘too large’ data types If a variable of a data type that is larger than a byte is mapped to a byte address, the value of the variable will be truncated to byte size there! For monitoring the variable value in the I/O Mapping dialog, this means the following: In the root element of the address, the value is displayed that the variable currently has in the project. The current individual bit values of the byte are displayed in succession in the bit elements below that, but this may not be sufficient for the entire variable value.

Note

If a UNION is represented by I/O channels in the mapping dialog, it depends on the device whether mapping to the “root” element is also possible.

  1. In a POU, declare, for example, a variable xBool4 of the type BOOL with which you wish to access an input of the target device from the application.

  2. To open the device editor, double-click the device object in the device tree, and then the <device name> I/O Mapping tab.

  3. Observe the Variable column with the display of the device input channels and device output channels , which can still be sorted by organizational nodes , depending on the device. We assume that there is a device input of the type BYTE. It is displayed with its individual bit addresses (bit channels) below the BYTE node.

  4. Note: When mapping structured variables, the editor prevents you from entering both the structure variable (example: %QB0) and individual structure elements (example: %QB0.1 and QB0.2). Therefore, if there is a main entry with a subtree of bit channel entries in the mapping table, then the following applies: Then you can specify a variable either into the line of the main entry, or into the lines of the subelements (bit channels), but not into both.

    You can now occupy either the entire channel with a variable of a suitable type OR its individual bit-channel addresses with suitable variables of the type BOOL or BIT. First of all, double-click a bit input channel in the Variables column.

    ⇒ An input field opens.

  5. In order to place an existing variable on the channel, you must enter the desired project variable with the complete path. Press F|PNG72/_cds_icon_three_dots.png| to open the Input Assistant. Select, for example, the variable Application.PLC_PRG.xBool4 declared in PLC_PRG.

    ⇒ The variable is inserted. The HMI symbol () is displayed in the Mapping column. The address is now struck through. That does not mean that the address is no longer available, because values of existing variables are managed at another memory space. But: in order to avoid ambiguities when writing the values, you should nevertheless not occupy the address with a further variable, especially in the case of outputs.

    Note: For compiler version V3.5 SP11 and later, the initialization value of the variables is used automatically as the default value when mapping to an existing variable. You can edit the Default value field only if you map to a new created variable or if no mapping is specified. In older versions, users had to specify explicitly that the default value and initialization value were identical.

  6. Delete the variable assignment again. Click the root of the channel, the BYTE node. Use the input assistant again to select the variable Application.PLC_PRG.byte_gotodevice.

    ⇒ The variable is inserted, all bit addresses of the main channel are struck through and you should not additionally occupy them.

See also

Mapping a device input to a recently created project variable

In the following you will map a device output to a global implicit variable, which you recently create for this purpose directly in the I/O Mapping dialog.

Note

The I/O Mapping dialog is thus a further place for declaring a global variable.

Requirement: A device that supports an I/O mapping configuration in CODESYS is inserted in the device tree of your project. On the I/O Mapping tab in the device editor you will thus see a tabular display of the input and output channels of the device with specification of the addresses and data types.

  1. To open the device editor, double-click the device object in the device tree, and then the <device name> I/O Mapping tab.

  2. Click in the mapping table on a channel entry in the Variable column in order to open an input field.

  3. Enter a simple name (without ‘.‘) for a new variable (for example, myBool).

    ⇒ CODESYS creates the variable as an implicit global variable in the project and assigns it directly to the channel address. Therefore in this case the address does not appear struck through as in the case of mappings to existing variables .

Linking a device with a function block instance

If supported by the device, you can map entire function blocks to an input or output channel. This allows you to count the frequency of signal changes or scale a channel value for maintenance purposes, for example.

Here you will map a device output channel to a function block. In this example, the block scales the channel output value.

A device with a digital output that supports FB mapping is linked in the project. There is a function block Scale_Output_Int with the following implementation. The attributes of the function block itself and before the output parameter with which the channel output is processed are important.

{attribute 'io_function_block'}
FUNCTION_BLOCK Scale_Output_Int
VAR_INPUT
    iInput : INT;
    iNumerator : INT;
    iDenominator : INT :=1;
    iOffset : INT := 0;
END_VAR
VAR_OUTPUT
 {attribute 'io_function_block_mapping'}
    iOutput : INT;
END_VAR
VAR
END_VAR
IF iDenominator <> 0 THEN
    iOutput := TO_INT(TO_DINT(iInput) * TO_DINT(iNumerator) / TO_DINT(iDenominator)) + iOffset;
  1. Open the <device name> I/O Mapping tab of the device editor. Double-click the output that should be connected to the function block. Click the button Add FB for IO channel.

    ⇒ The Select function block dialog opens. On the left side, you see at least the function block Scale_Output_int below the Application node. Libraries linked in the project that contain corresponding function blocks are also displayed for selection.

  2. Select the POU myScaleOutputInt.

    ⇒ After clicking OK, the path of the function block parameter iOutput in the Variable is entered in the mapping dialog. The path comprises the application name, the device channel name, and the selected FB output (example: App1.Out_4_Int_myScale_Output_Int_1.iOutput).

  3. Select the channel entry and click the button Go to instance.

    ⇒ The focus switches to the <device name> IEC Objects tab and the created entry for the new IEC object Out_4_Int_myScale_Output_Int_1. In online mode in this view, you see the current value of the parameter I scaled by the FB.Output for the Out_4_Int channel. You can also write and force the value as in other monitoring views.

See also

Changing and fixing an address value in the I/O map

You can change the address value of an entire channel (but not that of an individual subelement of the channel!) in the mapping table of the <device name> I/O Mapping tab. This allows you to adapt the addressing to a specified machine configuration and to retain the address value even if the layout of the modules changes. By default a change of the layout leads to an automatic adaptation of the address values.

Requirement: Your project has I/O mapping. Refer to the corresponding sections of the help page above.

  1. To open the device editor, double-click the device object in the device tree, and then the <device name> I/O Mapping tab.

  2. Click in the mapping table on a channel entry in the Address column in order to open an input field. This is only possible for the ‘root’ address of a channel, not for a particular one of its subelements!

    Therefore, change the top address entry of a channel in the table, for example from QB0 to QB1. Exit the input field.

    ⇒ The address value is changed. The symbol is displayed before the address. It indicates that the address is fixed. The addresses of the subelements of the channel are also changed accordingly. If you now change the position of the device object inside other device objects with input/output channels in the device tree, CODESYS does not adapt these addresses to the new order as would be the case without fixing.

  3. In order to undo the manual change or fixing, open the input field of the address value again, delete the address entry and press the Enter key.

    ⇒ CODESYS resets the address and the subsequent addresses concerned to the values they had before the change and removes the symbol .

See also

Configuration of the I/O variable update

Depending on the device that you link in the project, CODESYS updates the variables applied to its inputs and outputs in different ways. You can explicitly change the settings for this in the I/O Mapping dialog.

See also

Monitoring of variables in the I/O map in online mode

Requirement: You have compiled an application with a device configuration containing I/O maps without error. The associated hardware and the bus system are running. You have connected to the controller with the command Online ‣ Login and have loaded and started the application.

  1. Open the I/O Mapping tab of the PLC in the device editor. To open the editor, double-click the device object in the device tree.

    ⇒ The mapping table now additionally contains the columns Current value and New value.

    If a structure variable is mapped to the ‘root’ element of an address1, CODESYS does not display a value in this line in online mode. If, for example, a DWORD variable is mapped to the address, however, the respective values are monitored both in the ‘root’ line and in the indented bit-channel lines below it.

    As a matter of principle, the field in the ‘root’ line always remains empty if the value would be composed of several subelements.

    1 ‘root’ = top element of this address in the Mapping dialog

  2. Enter a certain variable value for an entry in the column New value and press F7 to force or Ctrl+F7 to write the value.

    ⇒ As in the case of monitoring in the declaration editor or in watch lists, the forced variable value is displayed in the column Current value with a prefixed red F-symbol or the written value.

Hint

Inputs and outputs that the PLC code does NOT use are not read by the PLC in online mode, as a result of which the displayed value could be incorrect. The Current value of the variables concerned is displayed with a gray background.

Generating implicit variables for the forcing of I/Os

During the commissioning of a plant or machine it may be necessary to ‘force’ the values applied at the inputs and outputs. If a device supports this you can cause special ‘force variables’ to be generated for this purpose and use them, for example, in an HMI visualization.

Requirement: The device supports this function. You have a project in which an I/O map is configured for the device and which contains a program object PLC_PRG.

  1. Open the device editor, PLC settings tab, by double-clicking the device object in the device tree.

  2. Activate the option Generate force variables for IO mapping.

  3. Press F11 to compile the application.

    ⇒ Two variables are created for each I/O channel in accordance with the following syntax, in the process of which spaces in the channel name are replaced by underscores:

    <device name>_<channel name>_<IEC address>_Force of type BOOL for the activation and deactivation of forces.

    <device name>_<channel name>_<IEC address>_Value of the data type of the channel for defining the value that you wish to force on the channel.

    These variables are available in the input assistant in the category Variables / IoConfig_Globals_Force_Variables. You can use them in CODESYS in programming objects, in visualizations, in the symbol configuration, etc.

  4. Open the function block PLC_PRG, set the focus in the implementation part and press F2.

    ⇒ The input assistant opens. The variables are available in the category Variables / IoConfig_Globals_Force_Variables as described above.

    A rising edge at the ‘Force variable’ input activates the forcing of the respective input or output with the value given by the ‘Value variable’. A falling edge deactivates the forcing. Deactivation by resetting the ‘Force’ variable to FALSE is the requirement for being able to force a new value!

Observe the following limitations!

  • Forcing via the implicit force variables is only possible for channels that are mapped in the I/O Mapping of the device to an existing or recently created variable.
  • Forcing via the implicit force variables is not possible for unused inputs and outputs or those that are mapped to a variable via an AT declaration in an application program.
  • I/O channels that you wish to force via the mechanism must be used by CODESYS in at least one task.
  • CODESYS identifies forced inputs in the monitoring by the red Force symbol, but not forced input/outputs! The forced value is used only implicitly by the I/O driver for writing to the device.

See also

I/O mapping in 1 dialog for several devices

There is a table that displays the I/O map of a device plus the I/O maps of all subelements inserted below it in the device tree. There you can edit the I/O maps in exactly the same way as in the individual mapping tables of the respective device editors.

Requirement: In the device tree of your project there are several PLCs inserted that each enable an I/O mapping configuration.

  1. Select the root node of the device tree and select the Edit IO mapping command in the context menu .

    ⇒ The Edit IO mapping dialog opens, in which the I/O mapping configurations of all devices inserted in the project are displayed in a table. You can edit the entries in the same way as in the I/O Mapping dialog of the associated device editor.

  2. Now select one of the control objects in the device tree and select the Edit I/O mapping command once again in the context menu.

    ⇒ The Edit IO mapping dialog now shows only the I/O table for the I/O mapping configurations found in and under the selected object.

  3. Set a desired Filter in the bar above the table or enter a variable name in the Search for variable field in order to see the use of this variable in the mapping.

    ⇒ The method of working in this window is the same as that described for the <device name> I/O Mapping tab.

See also